Parametric | TZ800N12KOF |
---|
VDRM / VRRM [V] | 1200.0 |
---|
IFAVM/TC / ITAVM/TC [A/°C]
(@180° el sin) | 800/85 |
---|
IFSM / ITSM [A]
(@10ms, Tvj max) | 30000.0 |
---|
∫I2dt [A²s · 103]
(@10ms, Tvj max) | 4500.0 |
---|
VT0 [V]
(@Tvj max)
max | 0.82 |
---|
rT [mΩ]
(@Tvj max)
max | 0.17 |
---|
(diT/dt)cr [A/µs]
(@DIN IEC 747- 6) | 200.0 |
---|
RthJC [K/W]
(@180° el sin)
max | 0.042 |
---|
Tvj [°C]
max | 125.0 |
---|
Housing | PowerBLOCK 70 mm |
---|
Configuration | Single SCR Phase Control |
---|
VDRM/ VRRM (V) | 1200.0V |
---|
IFSM / ITSM | 30000.0A |
---|
IFAVM / TC / ITAVM / TC | 800/85 (180° el sin) A/°C |
---|
Sales Product Name | TZ800N12KOF |
---|
OPN | TZ800N12KOFHPSA3 |
---|
Product Status | active and preferred |
---|
Package Name | BG-PB70AT-1 |
---|
Completely lead free | yes |
---|
Halogen free | no |
---|
RoHS compliant | yes |
---|
Packing Size | 1 |
---|
Packing Type | TRAY |
---|
Moisture Level | 1 |
---|
| Summary of Features:- Pressure contact technology for high reliability
- Industrial standard package
- Electrically insulated baseplate
- Short on fail
- Highest robustness
Benefits:- Fail safe
- Preventing arcing on fail
- Easy mounting
- Fuseless design possible due to high overload capability
- UL recognized
Benefits:- Fail safe
- Preventing arcing on fail
- Easy mounting
- Fuseless design possible due to high overload capability
- UL recognized