SE-135 Series - Ground-Fault Ground-Check Monitor

DataSheet:Littelfuse SE-135 Datasheet

The SE-134C/SE-135 is a microprocessor-based, combination ground-wire monitor and ground-fault relay for resistance grounded or solidly grounded systems. It continuously monitors the integrity of the ground conductor to protect portable equipment from hazardous voltages caused by ground faults. The SE-134C/SE-135 is field proven in monitoring trailing cables on large mobile equipment such as drag-lines, mining shovels, shore-to-ship power cables, dock-side cranes, stacker-reclaimers, submersible pumps, and portable conveyors.

COMPUTER TO RELAY CONNECTION

Connect the SE-135 to the network using a standard Ethernet patch cable. Use of a crossover cable to connect the SE-135 directly to the computer running SE-MON-GFGC is not recommended. A typical router will assign an IP address to all connected computers that are using DHCP. The SE-135 does not support the use of DHCP. If the SE-135 is being set-up for first time, it is recommended to only have one SE-135 connected to the network to prevent communication errors.

.

Ordering Information
Catalog #SupplyVoltage(VAC)SupplyVoltage(VDC)RelayContactsApprovalsCommsIEEE Device NumbersRelayContactOperatingMode
SE-135-00120 - 240120 - 240One Form A (N.O.); One Form B (N.C.); Two Form C (N.O./N.C.)CSA; UL; C-TICK; CE3GC50G50N51G51NFail-safeNon Fail-safe
SE-135-03120 - 240120 - 240One Form A (N.O.); One Form B (N.C.); Two Form C (N.O./N.C.)CSA; ULEthernet3GC50G50N51G51NFail-safeNon Fail-safe
SE-135-1024 - 48One Form A (N.O.); One Form B (N.C.); Two Form C (N.O./N.C.)CSA; UL3GC50G50N51G51NFail-safeNon Fail-safe
SE-135-1324 - 48One Form A (N.O.); One Form B (N.C.); Two Form C (N.O./N.C.)CSA; ULEthernet3GC50G50N51G51NFail-safeNon Fail-safe
Resources
Download PGM-8134 Datasheet pgm-8134
Download Drawing pma-8
Littelfuse-Protection-Relay-PGM-8134 pgm-8134
SE-135 Manual se-135
SE-135 Manual Chinese se-135
Littelfuse Protection Relays SE-135 CAD Drawing se-135
SE-ta6a CAD Drawing se-145
TN-GC-06 Replacing SE-125 with SE-135 se-135
TN GC-07 SE-134C Guideform Specification se-135
TN GC-08 Using GF GC Monitors Load Discrimination se-135
TN-GC09_Dual-Cable-Monitoring se-135
TN GC-13 Splitter-box dual-cable monitoring with an SE-135 se-135
TN-MA08_PMA-8-Atkinson-Omser-Adapter se-135
Littelfuse Protection Relays Ground-Fault Paper TN se-145
SE-135