PGR-3100 Series - Ground-Fault Indication System

DataSheet:Download PGR-3100 Datasheet

The PGR-3100 indicates the presence of voltage on each phase of a three-phase system. The LEDs on the panel illuminate when voltage is present. When a ground-fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim. On a resistance grounded or ungrounded system the LEDs for the unfaulted phases become brighter. Ungrounded ac systems are required by the National Electrical Code (NEC®) Article 250.21(B) and the Canadian Electrical Code Part 1, Section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to any system voltage. PTs are not required for system voltages up to 600 Vac.
Ordering Information
Catalog #SupplyVoltage(VAC)SupplyVoltage(VDC)RelayContactsApprovals
PGR-3100600 VacN/AN/ACSA; UL
Resources
Download PGR-3100 Datasheet pgr-3100
PGR-3100 Manual pgr-3100